IEEE Transactions on Energy Conversion, Vol.20, No.4, 887-895, 2005
Standby power system VRLA battery reserve life estimation scheme
This paper presents a valve-regulated lead acid (VRLA) batten, reserve life estimation scheme. The scheme is adaptive in both type and frequency of involvement. The scheme is based on capacity trending with the support of a number of state-of-health (SOH) indicators. These SOH indicators include accumulated thermal stress, float voltage, and indicators acquired from the start-of-discharge (coup de fouet) region. An implementation test case is given, indicating that the scheme is capable of providing an accurate estimation of reserve life long before the end of life. Furthermore, the estimation accuracy improves as the end of battery life approaches.