IEEE Transactions on Energy Conversion, Vol.22, No.1, 174-180, 2007
Short-circuit current of wind turbines with doubly fed induction generator
The short-circuit current contribution of wind turbines has not received much attention so far. This paper considers the short-circuit behavior, especially the short-circuit current of wind turbines with a doubly fed induction generator. Mostly, these wind turbines have a crowbar to protect the power electronic cone verter that is connected to the rotor windings of the induction generator. First, the maximum value of the short-circuit current of a conventional induction machine is determined. The differences between a crowbar-protected doubly fed induction generator and a conventional induction generator are highlighted and approximate equations for the maximum short-circuit current of a doubly fed induction generator are determined. The values obtained in this way are compared to the values obtained from time domain simulations. The differences are less then 15%.