화학공학소재연구정보센터
Process Safety and Environmental Protection, Vol.89, No.4, 268-274, 2011
Treatment of PCB-contaminated pole transformers by vacuum thermal recycling with voltage adjuster
In this study, we employed vacuum thermal recycling (VTR) with a voltage adjuster, herein referred to as the 'improved VTR method', to treat polychlorinated biphenyl (PCB)-contaminated pole transformers. We evaluated the performance of the improved VTR method for PCB removal using 50- and 75-kVA pole transformers containing 11.8 and 214.8 mg/L of PCBs, respectively. The total residual PCBs were below the detection limit for all samples: copper coil, iron core, insulating paper, wood, and porcelain. To increase the temperature of the copper coil from room temperature to 200-230 degrees C, 292-406 kWh of power was consumed for the conventional VTR method whereas 102-131 kWh was consumed for the improved VTR method. Further, the time required to heat the transformers under the same condition was 131 and 292 min for the improved and the conventional VTR method, respectively. The temperature increase was achieved by the improved VTR method at input energies of only similar to 5 kWh for the 75-kVA transformer and 3 kWh for the 50-kVA transformer. These results suggest that the improved VTR method is more cost-effective than the conventional VTR method because of its low power consumption and treatment time. (C) 2011 The Institution of Chemical Engineers. Published by Elsevier B.V. All rights reserved.