Applied Energy, Vol.102, 665-675, 2013
Borehole resistance and vertical temperature profiles in coaxial borehole heat exchangers
Ground source heat pump systems are often coupled to the ground by circulating a fluid through vertical Borehole Heat Exchangers (BHEs). The design of a system requires estimates of the ground thermal conductivity and the borehole thermal resistance, which are usually determined by an in situ thermal response test on a completed borehole. The usual test interpretation methods average the inlet and outlet fluid temperatures and use this mean temperature as the average temperature along the borehole length. This assumption is convenient but does not strictly apply. For a coaxial heat exchanger this paper develops an analytical model for the vertical temperature profiles, which can be used instead of the mean temperature approximation to estimate borehole resistance. The model is verified with measured temperatures on a BHE, where an optical technique allows continuous measurements along a coaxial borehole during a distributed thermal response test. A sensitivity study shows that the proposed method corrects errors in the mean temperature approximation, which overestimates the borehole resistance in a coaxial borehole. (c) 2012 Elsevier Ltd. All rights reserved.
Keywords:Ground-source heat pump;Ground heat exchanger;Borehole thermal resistance;Thermal response test;Borehole temperature profiles;Borehole heat transfer