Experimental performance analysis of a direct-expansion ground source heat pump in Xiangtan, China
The DX GSHP (direct-expansion ground source heat pump), which uses a buried copper piping network through which refrigerant is circulated, is one type of GSHP (ground source heat pump). This study investigates the performance characteristics of a vertical U-bend direct-expansion ground source (geothermal) heat pump system (DX GSHPS) for both heating and cooling. Compared with the conventional GCHP (ground coupled heat pump) system, the DX GSHP system is more efficient, with lower thermal resistance in the GHE (ground heat exchanger) and a lower (higher) condensing (evaporating) temperature in the cooling (heating) mode. In addition, the system performance of the whole DX GSHP system is also higher than that of the conventional GCHP system. A DX GSHP system in Xiangtan, China with a U-bend ground heat exchanger 42 m deep with a nominal outside diameter of 12.7 mm buried in a water well was tested and analysed. The results showed that the performance of this system is very high. The maximum (average) COPs of the system were found to be 6.08 (4.73) and 6.32 (5.03) in the heating and cooling modes, respectively. (C) 2013 Elsevier Ltd. All rights reserved.