화학공학소재연구정보센터
Renewable Energy, Vol.31, No.3, 285-305, 2006
Distributed control system for frequency control in a isolated wind system
High wind penetration wind diesel hybrid systems (WDHS) have three modes of operation: diesel only (DO), wind diesel (WD) and wind only (WO). The control requirements for frequency control in WO mode are analysed and a distributed control system (DCS) is proposed for this frequency control, describing the actuation of its sensor and actuator nodes. A power system for WO mode consisting of a wind turbine generator (WTG), a synchronous machine (SM), the consumer load, a battery based energy storage system (ESS) and a discrete dump load (DL) along with the associated DCS have been simulated. By means of a 400 Hz reference power message that establishes the active power necessary for frequency regulation and a prescribed active power sharing between the ESS and DL actuators, graphs for frequency, voltage and active powers for consumer load and wind speed changes are presented. The results of the simulation show maximum settling times and frequency per unit variation of 1.5 s and 0.16% respectively, for the previous input changes. The DCS solution presented could constitute a proposal for the standardization of the control for WO mode in high wind penetration WDHS which rely on a SM to generate the voltage waveform in that mode. (c) 2005 Elsevier Ltd. All fights reserved.