Energy and Buildings, Vol.93, 217-226, 2015
A numerical investigation of buoyancy induced turbulent air flow in an inclined passive wall solar chimney for natural ventilation
This paper reports a numerical investigation of the buoyancy induced turbulent air flow in an inclined passive wall solar chimney (IPWSC) attached to a room (ventilated space) for ventilation applications over a range of controlling parameters. The standard k - epsilon turbulence model has been employed to model air turbulence in the solar chimney system. With an isoflux heating condition specified on the absorber wall, the ventilation performance of the IPWSC design has been examined over the Rayleigh number range of 1.36 x 10(13) <= Ra <= 1.36 x 10(16) and inclination angles from 0 degrees to 6 degrees. The present numerical result shows that the turbulent kinetic energy and turbulent intensity in the solar chimney decrease with the increase of the inclination of the passive wall. The effectiveness of the IPWSC design for enhancing the thermally driven ventilation has been confirmed. Additional simulations have been carried out with a standalone solar chimney model. The result shows that the standalone model over-predicts the mass flow rate compared to that predicted by the attached model. The average difference in the predicted mass flow rates between the standalone model and the attached model with inclination angles from 0 to 6 degrees at a representative Rayleigh number of Ra = 1.36 x 10(14) is around 10%. (C) 2015 Elsevier B.V. All rights reserved.