Renewable Energy, Vol.87, 1053-1058, 2016
Performance of a solar air composite heat source heat pump system
For the shortcoming of air source heat pump in heating condition, a composite heat exchanger was designed which integrates fin tube and tube heat exchanger, and it can achieve synchronous and composite heat exchange in one heat exchanger between working fluids, gaseous and liquid heat source. With the above composite heat exchanger as the core component, the Solar Air Composite Heat Source Heat Pump System (SACHP) was developed which has three working modes, including single solar heat source mode, single air heat source mode and solar air dual heat sources mode. A SACHP experiment table was established and conducted a comprehensive experimental study of three working modes of this system in the standard enthalpy difference laboratory. The results show that when the ambient temperature was -15 degrees C, compared to the single air heat source mode, the dual heat source mode increased 62% in heat capacity and 59% in COP; when the temperature difference of combined heat transfer was -15 degrees C, compared to the single air heat source mode, the dual heat source mode increased 51% in heat capacity and 49% in COP. Experimental results demonstrate that the application of the solar air composite heat pump technology can accelerate the application process of the solar heat pump in air conditioners for buildings. (C) 2015 Elsevier Ltd. All rights reserved.