Energy and Buildings, Vol.127, 794-804, 2016
Energy and exergy based evaluation of the renovated Afyon geothermal district heating system
In this study, the exergy and energy analyses of the Renovated Afyon Geothermal Heating System (NAF-JET), which was completely renovated in the Afyon province of Turkey between the years 2011-2013, were conducted. The exergy destruction in the overall geothermal district heating system (GDHS) was quantified and illustrated using exergy flow diagrams. Both energy and exergy flow diagrams were presented for comparison purposes. The analyses revealed that the exergy destruction in the system took place particularly due to the exergy of the thermal water (geothermal fluid) re-injected, the heat exchanger losses, the losses of all pumps and pipeline loses, accounting for 15.94%, 12.44%, 5.52% and 5.52% of the total exergy input to the system. Both energy and exergy efficiencies of the overall system were investigated, and they were found to be 46.17% and 60.63%, respectively. (C) 2016 Elsevier B.V. All rights reserved.