Energy and Buildings, Vol.138, 579-590, 2017
Comparing methods of modeling air infiltration through building entrances and their impact on building energy simulations
Building entrance doors are a major source of air infiltration and energy loss in commercial buildings. Previous studies have calculated entrance doors air infiltration and energy saving potential of vestibules with the simplified method which is based on pressure factors. However, challenges are still faced in estimating the pressure difference and the resultant infiltration rates across doors as well as validating the used airflow coefficients under different flow conditions. In this paper, an experimental study is used to validate the airflow coefficient for a fully open single door under both infiltration and exfiltration conditions. The study presents four methods for modeling air infiltration across automatic single and vestibule doors for two reference building models: two methods use the pressure factors and the two others are based on airflow simulations. Energy simulations are then conducted using the air infiltration rates obtained from each method. The results revealed that the design methods overestimate the pressure difference across doors, the air infiltration rates as Well as the vestibule savings potentials in comparison to the simulation methods. In conclusion, airflow simulations were found to provide more realistic estimates of pressure differences and infiltration rates across entrance doors when compared to the widely-used design methods. (C) 2016 Elsevier B.V. All rights reserved.
Keywords:Air infiltration;Entrance doors;Vestibules energy savings;Experimental validation;Airflow and energy simulations