Energy and Buildings, Vol.146, 353-363, 2017
Investigation of liquid desiccant regenerator with heat recovery heat pipe system
To evaluate and compare the regenerator of liquid desiccant dehumidification system (LDDS) without and with heat pipe heat exchanger (HPHE), this paper conducts performance analysis by hybrid heat transfer, mass transfer and heat recovery models, and the simulation results are then validated by the experimental results. 4 and 8 rows HPHE are compared to investigate the relationship between heat recovery rate and the additional fan energy consumption caused by the existence of HPHE. Effects of air mass flow rate on the regenerating and heat recovery performance are also discussed. The results show that the numerical computation is effective and accurate and the largest RE is only 10.87%. With heat recovery device, the regenerating performance is in general improved. The model predicted results reveal that the maximal net heat recovery ratios are 25% and 26.5% which contributes to 26.5% and 27% maximal energy saving for 4 and 8 rows, respectively, compared with regenerator without HPHE. (C) 2017 Elsevier B.V. All rights reserved.
Keywords:Liquid desiccant dehumidification system;Regenerator;Heat recovery;Heat pipe heat exchanger;Numerical investigation;Performance analysis