Applied Energy, Vol.213, 31-44, 2018
Thermodynamic feasibility evaluation of hybrid dehumidification - mechanical vapour compression systems
Air conditioning approach using two separate units for latent heat and sensible heat removal opens up opportunities and challenges for improved efficiency. In such systems, the dehumidification device removes moisture from the air stream usually without condensation whilst the remaining sensible load is handled by a conventional mechanical vapour compression (MVC) machine. This article investigates the thermodynamic feasibility of such hybrid dehumidifier + MVC systems as potential replacements for the conventional MVC devices. We shed some light on the minimum efficacy requirement in terms of COP or simply the breakeven COP for the coupled dehumidification system. Thermodynamic investigation has been conducted using classical Carnot, endoreversible technique and the experimental approaches. The breakeven COPs for a dehumidifier + MVC system where the latter using HFC-R14a, HFC-R32 and HFO-R1234yf as refrigerants have been investigated at assorted outdoor air ratios. Performance enhancement in terms of COP and the cooling capacity at elevated temperatures for sensible cooling are accounted for. It is observed that the breakeven COP for the dehumidification system ranges from 9 to 17 (Carnot approach) and 4.3 to 6.8 (Ideal cycle) in order to be realistically competitive with the current efficiency offered by a MVC system for the both dehumidification and sensible cooling. The life cycle cost (LCC) analysis is further performed to assess the fresh air-handling systems using a conventional MVC system and a dehumidifier + MVC system. The unprecedented improvement in the performance of the MVC systems further raises the ceiling for the breakeven COP of the dehumidification systems.
Keywords:Breakeven COP;Chiller efficiency;Decoupling latent heat;Isothermal dehumidification;Mechanical vapour compression