화학공학소재연구정보센터
Renewable Energy, Vol.118, 265-277, 2018
Performance assessment of a photonic radiative cooling system for office buildings
Recent advances in materials have demonstrated the ability to maintain radiator surfaces at below ambient temperatures in the presence of intense, direct sunlight. Daytime radiative cooling is promisifig for building applications. This paper estimates the energy savings from daytime radiative cooling, specifically based on photonic materials. A photonic radiative cooling system was proposed and modeled using the whole energy simulation program EnergyPlus. A typical medium-sized office building was used for the simulation analysis. Several reference systems were established to quantify the potential of energy savings from the photonic radiative cooling system. The reference systems include a variable-air volume (VAV) system, a hydronic radiant system, and a nighttime radiative cooling system. The savings analysis was made for a number of locations with different climates. Simulation results showed that the photonic radiative cooling system saved between 45% and 68% cooling electricity relative to the VAV system and between 9% and 23% relative to the nighttime radiative cooling system featured with the best coating commercially available on market. A simple economic analysis was also made to estimate the maximum acceptable incremental cost for upgrading from nighttime cooling to photonic radiative cooling. (C) 2017 Elsevier Ltd. All rights reserved.