화학공학소재연구정보센터
Journal of Power Sources, Vol.116, No.1-2, 8-13, 2003
Lead-acid battery research and development - a vital key to winning new business
Battery strings are operated in a partial-state-of-charge mode (PSoC) in several new and changing applications for lead-acid batteries, in which the battery is seldom, if ever, fully charged or discharged. The lead battery industry faces new challenges as additional failure modes become evident in these PSoC applications. Without overcharge, cell imbalances caused by variations in cell temperature will cause premature failures. Valve-regulated lead-acid batteries are especially susceptible because of the heat generated by oxygen recombination at the negative plate. Improved thermal properties are shown by a proprietary battery design that combines absorptive glass mat and gelled acid technologies. Well-designed power systems are also required to reduce cell-to-cell temperature variations and, thereby, increase battery life. (C) 2002 Published by Elsevier Science B.V.