Energy consumption and ventilation performance of a naturally ventilated ecological house in a cold climate
In this paper, the thermal and ventilation performance of an ecological house in Helsinki, Finland are presented. The single-family dwelling has a well-insulated, wooden frame construction with no plastic vapour retarder. The measured and simulated results show that the energy consumption of the house is low and that the outdoor ventilation rate is generally satisfactory based on the measured CO2 concentrations. Extrapolating the measured ventilation data shows that, when the operable windows are closed, the ventilation rate is expected to be about 0.45 air-changes-per-hour (ach) in the winter and about 0.25 ach in the summer. The consumption of total primary energy and space heating energy were measured to be 30% less (162 kWh/(m(2) a)) and 36% less (76 kWh/(m(2) a)) than in typical Finnish houses, respectively. The paper also uses a numerical model to investigate the sensitivity of energy consumption to the insulation level, household electricity and domestic hot water consumption, window area, ventilation rate and heat recovery effectiveness. (C) 2004 Elsevier B.V. All rights reserved.