Chemical Engineering Research & Design, Vol.78, No.4, 528-541, 2000
Process identification from closed-loop response using optimization methods
Existing methods employ different approaches and analyses for closed-loop identification of a suitable model such as a second order plus dead time (SOPDT) model for a single-input single-output (SISO) process. In this study, an optimization approach for identifying a SOPDT model from closed-loop response is proposed and its performance is extensively evaluated mainly via simulation. Typical examples, test conditions, controller and response types, step and relay responses as well as measurement noise are considered. Three optimization methods, namely, the multi-pass LJ method (which finds the global minimum), modified Simplex method and a quasi-Newton method are tried. The results show that the recovered model is more accurate than those obtained by other methods, and that a reliable and consistent model can be obtained even from the response with measurement noise, At least two minima are likely when step response is used and several minima are probable when relay response is employed. The optimization approach is independent of the nature of the closed-loop response and controller used in the test, be it a PSD controller or a relay. importantly, the test duration can be considerably shortened because the step test need not be conducted until steady state, and in the relay test, steady oscillations are not required.
Keywords:ONLINE PROCESS IDENTIFICATION;RELAY FEEDBACK;AUTOTUNEIDENTIFICATION;PID CONTROLLERS;TUNING METHOD;DIRECT SEARCH;SYSTEMS;MODEL;DERIVATION;SINGLE