Applied Energy, Vol.83, No.3, 239-252, 2006
Boiling heat-transfer coefficient variation for R407C inside horizontal tubes of a refrigerating vapour-compression plant's shell-and-tube evaporator
The present paper presents experimental results obtained from a refrigerating vapour-compression plant's shell-and-tube (1-2) evaporator working with R407C. Several tests have been carried out to study the influence of the evaporating pressure and the refrigerant's mass flow rate on the refrigerant's boiling heat-transfer coefficient inside horizontal tubes. This work has been performed by analyzing the variations of the evaporator's overall thermal-resistance, computed using the effectiveness-NTU method, considering the influence of pressure drops and glide at the evaporator, and finally transferring the results and conclusions to the boiling heat-transfer coefficient. It has been observed that the variations of the boiling heat-transfer coefficient show a dependence on the evaporating temperature and the refrigerant's mass-flow rate, which has been analyzed in the test range. (C) 2005 Elsevier Ltd. All rights reserved.
Keywords:shell-and-tube heat-exchanger;R407C;boiling heat-transfer coefficient;overall heat-transfer coefficient;refrigeration vapour-compression plant