화학공학소재연구정보센터
Energy and Buildings, Vol.41, No.6, 596-606, 2009
Evaluation of alternative arrangements of a heat pump system for plume abatement in a large-scale chiller plant in a subtropical region
Heat pumps could be used to produce hot water for hybrid cooling towers for preventing the occurrence of plume in subtropical regions. The evaporative side of the heat pump system could be arranged either at the inlet side or at the outlet side of these cooling towers for cooling down the cooling water temperature. Alternatively, the evaporative side of the heat pump system could also be arranged at the evaporative side of chillers to reduce return chilled water temperature and therefore to reduce the cooling load of chillers. This study presents the evaluation of the impacts of these three arrangements of the heat pump system on the Plume control performance and the energy performance in a large-scale chiller plant in Hong Kong. The performance prediction and evaluation of the chiller plant and the plume abatement system were conducted on a dynamic simulation platform. The results show that these three arrangements have almost the same plume control performance with sufficient plume control capability. The results also show that the arrangement of the evaporative side of the heat pump system for cooling down return chilled water temperature has much better performance that the other two arrangements for improving the overall energy efficiency. (C) 2008 Elsevier B.V. All rights reserved.