화학공학소재연구정보센터
Energy and Buildings, Vol.42, No.4, 441-448, 2010
Conduction-corrected modified effective temperature as the indices of combined and separate effect of environmental factors on sensational temperature
In living spaces, people sit or lie on the floor and adopt a posture in which much of the surface of the body is in contact with the floor. When the temperature of the spatial structure or the surface temperature of an object in contact with the human body is not equivalent to the air temperature, these effects are non-negligible. Most research examining the physiological and psychological responses of the human body has involved subjects sitting in chairs. Research that takes into account body heat balance and assessments of thermal conduction into the environment is uncommon. Thus, in this study, conduction-corrected modified effective temperature (ETF), which is a new thermal environmental index incorporating heat conduction, is defined in order to make possible the evaluation of thermal environments that take into account different postures. This sensational temperature index converts the effects of the following parameters into a temperature equivalent: air velocity, thermal radiation, contact material surface temperature and humidity. This index has the features of a summation formula. Through the use of these parameters, it is possible to represent and quantify their composite influence on bodily sensation and the effects of discrete meteorological elements through an evaluation on an identical axis. (c) 2009 Elsevier B.V. All rights reserved.