Energy and Buildings, Vol.42, No.6, 799-806, 2010
Parametric studies and evaluations of indoor thermal environment in wet season using a field survey and PMV-PPD method
Fanger's PMV-PPD is the most famous thermal sensation indices but it is too complex to be applied in practice. To obtain simple and applicable correlations, taking Qujing of Yunnan province, China, as example, a wet season (six-month) field measurement was conducted in a naturally ventilated residential room. Based on collected data, PMV indices were calculated by using Newton's iterative method. It is shown that the PMV values approximately vary from -1.0 to +1.0 and the indoor thermal environment is basically comfortable. Relationships of the parameters (indoor and outdoor air temperatures, mean radiant temperature. PMV and PPD) and indoor air temperature gradients (vertical and horizontal) were also studied by means of the linear regression and the quadratic polynomial fit techniques. Numerous correlations with high relativities have been developed. Moreover, the vertical and horizontal air temperature gradients range from 0.1 K/m to 0.85 K/m and from -0.208 K/m to 0.063 K/m in wet season. It is convenient to use these results to evaluate and assess the indoor thermal environment under similar climatic conditions. The results of this work enrich and develop the basic theory of the indoor thermal environment design and control. (C) 2009 Elsevier B.V. All rights reserved.