화학공학소재연구정보센터
Energy Conversion and Management, Vol.51, No.7, 1500-1509, 2010
Part load efficiency of packaged air-cooled water chillers with inverter driven scroll compressors
In this paper different packaged air-cooled systems, operating on scroll compressors, are experimentally analysed from the point of view of the relation between energy efficiency and actual capacity. Single compressor, double compressors and double compressors with uneven volumetric capacity units are tested. Experimental tests demonstrated that cooling capacity control by means of variation of rotational speed is an suitable solution for improving the part load efficiency of these systems. Step capacity units obtained by splitting the system volumetric capacity between two compressors are also effective solutions. Nevertheless they appear to be more efficient than single inverter driven chillers only for part load conditions lower than 60%. In the analysed cooling capacity range (25-50 kW), tandem compressors chillers with one inverter driven compressor appear the most efficient solution combining rotational speed with step capacity control. Seasonal energy efficiency ratios were obtained with prEN 14825 calculation method confirming reduced energy consumption associated to continuous and step cooling capacity control. (C) 2010 Elsevier Ltd. All rights reserved.