화학공학소재연구정보센터
Energy, Vol.36, No.7, 3985-3991, 2011
A new scheme for cooling tower water conservation in arid-zone countries
Cooling towers (CTs) that are used for heat rejection in water-cooled (WC) systems consume a large quantity of water, which is generally not available naturally. CTs are selected when the maximal cooling load is desired and under the worst design conditions. Typically, CTs operate under partial-load conditions and/or favorable weather conditions. Moreover, for most of the summer season, the dry bulb temperature (DBT) of the incoming ambient air is significantly greater than the incoming hot water temperature, and the air undergoes sensible cooling. Currently, the control scheme that is commonly used in most as maintains a constant exiting water temperature for different cooling loads and a different ambient wet bulb temperature (WBT) by regulating the air circulation through the CT. The air circulation is reduced with the help of a variable frequency drive (VFD), which results in a significant reduction in the fan power of the CT. This paper presents an assessment of CT performance with a VFD application using a computer simulation program and illustrates a proposed scheme for maximal water savings. These theoretical results demonstrated that reducing the air flow by applying a VFD in a CT can achieve at least a 25% reduction in water consumption. (C) 2011 Elsevier Ltd. All rights reserved.