Heat Transfer Engineering, Vol.26, No.3, 28-35, 2005
Condensation pressure drop in circular microchannels
This paper presents a multiple flow-regime model for pressure drop during the condensation of refrigerant R134a in horizontal microchannels. Two-phase pressure drops were measured in five circular channels ranging in hydraulic diameter from 0.5 mm to 4.91 mm. For each tube under consideration, pressure drop measurements were first taken over the entire range of qualities from 100% vapor to 100% liquid for five different refrigerant mass fluxes between 150 kg/m(2) -s and 750 kg/m(2) -s. Results from the previous work by the authors on condensation flow mechanisms in microchannel geometries were used to assign the applicable flow regime to the data points. Pressure drop models for intermittent [1] and annular [21 flow reported earlier by the authors were modified and combined to develop a comprehensive model that addresses the entire progression of the condensation process from the vapor phase to the liquid phase. This combined model accurately predicts condensation pressure drops in the annular, disperse wave, mist, discrete waive, and intermittent flow regimes. Overlap and transition regions between the respective regimes are also addressed using an appropriate interpolation technique that results in relatively smooth transitions between the predicted pressure drops. The resulting model predicts 82% of the data within +/-20%.