Heat Transfer Engineering, Vol.31, No.2, 108-118, 2010
The Effect of the Electrohydrodynamic on the Two-Phase Flow Pressure Drop of R-134a during Evaporation inside Horizontal Smooth and Micro-Fin Tubes
This article concerns the pressure drop caused by using the electrohydrodynamic (EHD) technique during evaporation of pure R-134a inside smooth and micro-fin tubes. The test section is a counter-flow concentric tube-in-tube heat exchanger where R-134a flows inside the inner tube and hot water flows in the annulus. A smooth tube and micro-fin tube having an inner diameter of 8.12 mm and 8.92 mm, respectively, are used as an inner tube. The length of the inner tube is 2.50 m. The outer tube is a smooth copper tube having an inner diameter of 21.2 mm. The electrode, which is a cylindrical stainless steel wire having diameter of 1.47 mm, is placed in the center of the inner tube. The electrical field is established by connecting a DC high voltage power supply of 2.5 kV to the electrode while the inner tube is grounded. Experiments are conducted at saturation temperatures of 10-20 degrees C, mass fluxes of 200-600 kg/m(2)s, and heat fluxes of 10-20 kW/m(2). The experimental results indicate that the application of EHD introduces a small pressure drop penalty. New correlations for the pressure drop are proposed for practical applications.