초록 |
In this study, new Chung's equations-III and Chung's equation-IV of dimensionless indexes were established to comprehensively evaluate the risk of fire in a fire. First, the fire performance index-III (FPI-III) was evaluated by dividing the performance index-II (FPI-II) value by [FPI-II]PMMA based on PMMA. Second, fire growth index-III (FGI-III) was evaluated by dividing the fire growth index-II (FGI-II) value by [FGI-II]PMMA based on PMMA. In addition, the fire risk index-IV (FRI-IV) according to Chung's equation-IV is the FPI-III for the FGI-III of combustible objects. In conclusion, this study intends to base the data by utilizing the newly established fire risk assessment theory as described above, and to use it for building design and fire prevention measures.
|